# User manual СИ30

## Contents

- [Introduction](#topic-39668)
- [Safety instructions](#topic-39669)
- [Purpose and functions](#topic-39670)
- [Specifications and operating conditions](#topic-39671)
  - [Specifications](#topic-39672)
  - [Operating conditions](#topic-39673)
- [Safety measures](#topic-39674)
- [Mounting](#topic-39675)
  - [Installation of device in housing Н](#topic-39676)
  - [Installation of device in housing Щ1](#topic-39677)
  - [Installation of device in housing Щ2](#topic-39678)
- [Electrical connections](#topic-39679)
  - [Wiring recommendations](#topic-39680)
  - [Getting Started](#topic-39681)
  - [Pin assignment](#topic-39682)
  - [Connection of switching devices and sensors](#topic-39683)
  - [Connecting load to the outputs](#topic-39684)
- [Operation of the device](#topic-39685)
  - [Principle of operation](#topic-39686)
  - [Control and indication](#topic-39687)
  - [Switch on and operation](#topic-39688)
- [Setup](#topic-39689)
  - [Sequence of setup](#topic-39690)
  - [Operating modes](#topic-39691)
  - [Configuring the device from PC](#topic-39692)
- [Maintenance](#topic-39693)
- [Marking](#topic-39694)
- [Packaging](#topic-39695)
- [Transportation and storage](#topic-39696)
- [Scope of delivery](#topic-39697)
- [Warranty](#topic-39698)
- [Device parameters](#topic-39699)

<a id="topic-39668"></a>

## Introduction

This user manual is intended to familiarize service personnel with the design, principle of operation, structure, operation and maintenance of the pulse counter **СИ30** (further in the text called «device»).

Connection, setup and maintenance should be made only by qualified specialists after reading this manual.

The device is produced in various modifications, that are encrypted in code of full conventional designation.

![Маркировка 0000001553](https://docs.owen.ru/book_img/813/100649.png)

**Power supply:**

- **220** – 90...250 V AC, 50 Hz;
- **24** – 10,5...30 V DC.

**Construction type:**

- **Н** – wall-mounting housing;
- **Щ1** – panel-mounting housing (square front panel, 96x96 mm);
- **Щ2** – panel-mounting housing (rectangular front panel, 96x48 mm).

**Built-in outputs:**

- **Р** – electromagnetic relay;
- **К** – transistor optocoupler of *n-p-n* type;
- **С** – triac optocoupler.

The example of designation used for ordering and in other products documentation:

Pulse counter **СИ30-220.Щ2.Р ТУ 4278-007-46526536-2010**.

<a id="topic-39669"></a>

## Safety instructions

Following symbols and keywords are used in this manual:

> [!CAUTION]
> **Danger.** Keyword DANGER is used to warn about an imminent threat to health. Possible consequences may include death, permanent or prolonged incapacity for work.

> [!WARNING]
> **Caution.** Keyword CAUTION is used to prevent a potentially dangerous situation. Possible consequences may include minor injuries.

> [!IMPORTANT]
> **Notice.** Keyword NOTICE is used for supplement, clarifying, interpretation of the main text and/or clarifying specific aspects of working the device operation.

> [!NOTE]
> **Note.** NOTE indicates helpful tips and recommendations, as well as information for efficient and trouble-free operation.

<a id="topic-39670"></a>

## Purpose and functions

The device is a universal counter that can be used for a wide range of automation tasks. It is designed to count the number of pulses coming to its inputs in direct and opposite direction and to convert further this number into a physical value (using multiplication by given multiplier).

The device can perform following functions:

- count-up, count-down, reversing and other types of counting pulses from the connected sensors;
- determination of the direction of rotational motion of units and mechanisms;
- converting the number of pulses into real units of measurement;
- powering sensors from the built-in 24 V DC power source;
- load control by two built-in outputs;
- saving counting results when power is turned off;
- connection to PC via embedded RS-485 and USB interfaces.

<a id="topic-39671"></a>

## Specifications and operating conditions

<a id="topic-39672"></a>

### Specifications

Main specification of the device is given in [Table](#ХарактеристикиПрибора-2A1CA889).

<a id="ХарактеристикиПрибора-2A1CA889"></a>

**Device features**

**Power supply**

| **Item** | **Value** |
| --- | --- |
| AC:<br>• supply voltage<br>• frequency | 90...250 V<br>(nominal - 110, 220 or 240 V)<br>47...63 Hz (nominal - 50 and 60 Hz) |
| DC | 10.5...30 V |
| Power consumption, max. | 12.5 VA |

**Inputs**

| **Item** | **Value** |
| --- | --- |
| Number of control inputs | 4 |
| Logical 0 | 0...4 V |
| Logical 1 | 10...30 V |
| Current for sensor’s polling | 2 mA |
| Nominal supply voltage of the sensors | 24 V |
| Instability of sensor supply voltage | 10 % |
| Load current for power supply of sensors, max. | 100 mA |

**Outputs**

| **Item** | **Value** |
| --- | --- |
| Number of outputs | 2 |
| Current switched by relay contacts, max. | 8 A (220 V AC, cos φ > 0.4) |
| Current of transistor optocoupler load, max. | 0.2 A (at 50 V) |
| Current of optotriac load, max.:<br>- at 240 V (constantly open triac)<br>- if the triac is switched on with frequency = 50 Hz max and t<sub>imp</sub> = 5 ms | 50 mA<br>0.5 A |

**Pulse counter**

| **Item** | **Value** |
| --- | --- |
| Number of display digits | 6 |
| Counting speed, max. | 10 000 Hz |
| Duration of input pulses, min. | 50 µs |
| Range of values of the multiplier | from 0.00001 to 99999 |
| Frequency of input filter | from 1 to 50000 Hz |
| Pulse ratio, min. | 2 |
| Limit of permissible basic error (according to GOST 24907) | ±1 junior digit |
| Basic reduced error for measurement of time intervals | ±1% from 0.1 to 999.99 сtr |

**Housing**

| **Item** | **Value** |
| --- | --- |
| Dimensions:<br>• wall-mounting Н<br>• panel-mounting Щ1<br>• panel-mounting Щ2 | 105х130х65 mm<br>96х96х70 mm<br>96х48х100 mm |
| Protection class:<br>• wall-mounting Н<br>• panel-mounting Щ1 and Щ2 | IP44<br>IP54 (front panel side) |

**Device features**

| **Item** | **Value** |
| --- | --- |
| Weight, max. | 1 kg |
| Average service life | 8 years |
| Calibration interval | 2 years |

<a id="topic-39673"></a>

### Operating conditions

The device must be used in following conditions:

- closed explosion-proof areas without aggressive vapors and gases;
- ambient temperature from -20 to +70 °С;
- upper limit of relative humidity = max. 95% at 35°C and lower temperatures without moisture condensation;
- atmospheric pressure from 84 to 106.7 kPa.

In terms of resistance to mechanical influences during operation the device corresponds to group of performance N2 in GOST R 52931-2008.

> [!IMPORTANT]
> **Notice.** It is necessary to comply with the requirements for operating conditions, as they are part of safety measures.

<a id="topic-39674"></a>

##  Safety measures

> [!WARNING]
> **Caution.** The terminal block has life-threatening voltage up to 250 V. Any connections to the device and maintenance work should be carried out only when the power is turned off.

By the method of protection from electric shock the device corresponds to class II according to GOST 12.2.007.0-75.

While operating, maintaining and checking, it is necessary to comply with GOST 12.3.019-80, Rules of the technical operation of electrical consumers and Safety rules for operating electrical equipment.

There must be no moisture on the output terminals and the internal components of the device. It is forbidden to use the device in corrosive environments with acids, alkalis, oils , etc. in the air.

<a id="topic-39675"></a>

## Mounting

<a id="topic-39676"></a>

### Installation of device in housing Н

For installation of the device perform following actions:

![Монтаж копруса Н 0000001552](https://docs.owen.ru/book_img/813/100648.png)

*Installation of wall-mounting device*

1. Fasten the bracket on the surface intended for mounting with three M4 × 20 screws (see [Figure](#ПриборНастенногоКрепленияН-0EE6F648)).

   > **Notice.** Screws for bracket are not included in the package.

2. Hook the fixing bracket from the back panel of device to the upper edge of the wall bracket.

3. Attach device to the bracket with the supplied screw.

Demount the device in the reverse order.

> [!IMPORTANT]
> **Notice.** Remove the cover before wiring. Fasten the base of the device to the bracket with a supplied screw.

<a id="ПриборНастенногоКрепленияН-0EE6F648"></a>

![Габариты Н 0000001581](https://docs.owen.ru/book_img/813/100647.png)

*Dimensions of H housing*

> [!IMPORTANT]
> **Notice.** The bushings need to be cut in accordance with the diameter of the lead-in cable.

<a id="topic-39677"></a>

### Installation of device in housing Щ1

For installation of the device perform following actions:

![Монтаж Щ1 0000001580](https://docs.owen.ru/book_img/813/100646.png)

*Installation of panel-mounting device*

1. Prepare a place for mounting on the control panel (see [Figure](#ГабаритныеРазмерыКорпусаЩ1-41DA1A85)).
2. Install the gasket on the frame of the device to ensure degree of protection IP54.
3. Insert the device into a specially prepared hole on the front of the control panel.
4. Insert the supplied retainers into holes on the sides of the device.
5. Tighten supplied screws M4 x 35 in the holes of each retainer so that the device is pressed firmly to the front of the control panel.

Demount the device in the reverse order.

<a id="ГабаритныеРазмерыКорпусаЩ1-41DA1A85"></a>

![Габариты Щ1 0000001579](https://docs.owen.ru/book_img/813/100645.png)

*Dimensions of Щ1 housing*

![Щ1 в щите 0000001578](https://docs.owen.ru/book_img/813/100644.png)

*Device in Щ1 housing mounted in the control panel with 3 mm thickness*

<a id="topic-39678"></a>

### Installation of device in housing Щ2

For installation of the device perform following actions:

![Монтаж копруса Щ2 0000001577](https://docs.owen.ru/book_img/813/100643.png)

*Installation of panel-mounting device*

1. Prepare a place for mounting on the control panel (see [Figure](#ПриборВКорпусеЩ2УстановленныйВЩитТо-0EE7443F)).
2. Install the gasket on the frame of the device to ensure degree of protection IP54.
3. Insert the device into a specially prepared hole on the front of the control panel.
4. Insert the supplied retainers into holes on the sides of the device.
5. Tighten supplied screws M4 x 35 in the holes of each retainer so that the device is pressed firmly to the front of the control panel.

Disassemble the device in the reverse order.

![Габариты Щ2 0000001576](https://docs.owen.ru/book_img/813/100642.png)

*Dimensions of Щ2 housing*

<a id="ПриборВКорпусеЩ2УстановленныйВЩитТо-0EE7443F"></a>

![Щ2 в щите 0000001575](https://docs.owen.ru/book_img/813/100671.png)

*Device in Щ2 housing mounted in the control panel with 3 mm thickness*

<a id="topic-39679"></a>

## Electrical connections

<a id="topic-39680"></a>

### Wiring recommendations

To ensure the reliability of electrical connections it is recommended to use copper multicore cables, the ends of which should be carefully cleaned, tinned, otherwise use cable lugs before connection. Stripping of conductors must be performed in such way that the stripped ends after connecting to the device do not protrude beyond the terminal block. Cable cross section should be no more than 1 mm<sup>2</sup>.

General requirements for connection lines:

- During the cabling, communication lines that connect the device with sensors must be isolated to a separate circuit (or several circuits) and placed separately from power cables or other sources of high-frequency and impulse interferences.
- To protect the device inputs from the effects of industrial electromagnetic interference, the communication lines between device and sensors should be screened. Special cables with shielding or grounded steel pipes of suitable diameter can be used as screens. The cable shielding should be connected to the functional ground terminal (FE) in the control panel.
- Network interference filters should be installed in the power supply lines.
- It is necessary to install spark-suppression filters in the lines of switching of power equipment.

When mounting the system in which the device is used, the rules for effective grounding should be taken into account:

- all grounding lines must be laid in Y-connected circuit, ensuring good contact with the grounding element;
- all earthing circuits must be made with wires of the largest possible cross-section;
- it is forbidden to connect the device terminal "Common" with grounding lines.

<a id="topic-39681"></a>

### Getting Started

> [!CAUTION]
> **Danger.** After unpacking the device, make sure that it has not been damaged during transportation.

If the device has been for a long time at a temperature below minus 20 °C, it is necessary to keep it in a room with a temperature corresponding to the operating range for at least 30 minutes before switching on and operation.

For connecting the device perform following actions:

1. Connect the device to a power source.

   > **Caution.** Before powering up the device, it is necessary to check the correct connection of the supply voltage and its level.

2. Connect the "device - sensors" communication lines to the sensors and to device inputs.

3. Connect the "device - load" communication lines to the actuators and to outputs of the device.

4. Apply power to the device.

5. Set up the device.

6. Power off the device.

<a id="topic-39682"></a>

### Pin assignment

Screw terminals are located on the back wall of the panel-mounting device or inside the device (wall-mounting). The terminal block contacts assignment is shown in [Figure](#НазначениеКонтактовКлеммника-3B3A6AEF).

<a id="НазначениеКонтактовКлеммника-3B3A6AEF"></a>

![Контакты клеммника 0000001574](https://docs.owen.ru/book_img/813/100670.png)

*Terminal block contacts assignments*

<a id="topic-39683"></a>

### Connection of switching devices and sensors

> [!WARNING]
> **Caution.** Supply voltage on the device inputs (pins 9 – 12 at the terminal block) must be in range from 0 to 24 V.

> [!IMPORTANT]
> **Notice.** To supply the switching devices and sensors to the screw terminal block of the device is provided with supply voltage (pin 13 of the terminal block). If power consumption of input exceeds the load capacity of the built-in power supply (24 V), then an external power supply with an output voltage of 12 to 34 V (24 V recommended) must be used for powering.

Scheme for connection of the switching devices to the inputs is shown in [Figures](#ПодключениеКоммутационныхУстройствТ-41E5250F) [and](#ПодключениеКоммутационныхУстройствА-3B3A88F5) .

<a id="ПодключениеКоммутационныхУстройствТ-41E5250F"></a>

![Вход переключатели 0000001573](https://docs.owen.ru/book_img/813/100669.png)

*Connection of "dry contact" switching devices*

<a id="ПодключениеКоммутационныхУстройствА-3B3A88F5"></a>

![Вход коммутац 0000001572](https://docs.owen.ru/book_img/813/100668.png)

*Connection of switching devices: a) for operation with n-p-n sensors; b) for operation with p-n-p sensors*

Scheme for connection of passive and active sensors with an output *n-p-n* open-collector transistor or *p-n-p* is shown in [Figures](#ПодключениеДатчиковСN-p-n-выходомАП-3B3A8A75) [and](#ПодключениеДатчиковСP-n-p-выходомАП-3B3A8CA6) accordingly.

<a id="ПодключениеДатчиковСN-p-n-выходомАП-3B3A8A75"></a>

![Вход npn 0000001601](https://docs.owen.ru/book_img/813/100667.png)

*Connection of n-p-n-sensors: a) active; b) passive*

<a id="ПодключениеДатчиковСP-n-p-выходомАП-3B3A8CA6"></a>

![Вход pnp 0000001600](https://docs.owen.ru/book_img/813/100666.png)

*Connection of p-n-p-sensors: a) active; b) passive*

Device has a dual switch for selecting, which of the types of sensors will work. It is located on the lateral side of the housing Щ1 and Щ2. For device in the H housing, the switch is located inside the housing (to access the switch, it is necessary to remove the device cover by unscrewing the four screws that fasten the cover to the base). Appearance of the switch is shown in [Figure](#ВнешнийВидПереключателя-3B3A8EE2).

<a id="ВнешнийВидПереключателя-3B3A8EE2"></a>

![+Переключатель 0000001599](https://docs.owen.ru/book_img/813/100665.png)

*Dual switch*

Positions of the switch depending on which device operates with different sensors, are shown in [Table](#СостояниеПереключателяДляРазныхТипо-3B3A9075).

<a id="СостояниеПереключателяДляРазныхТипо-3B3A9075"></a>

**Switch status for different types of sensors**

|   |   |
| --- | --- |
| **Type of sensors** | **Switch positions** |
| *n-p-n* | 1 – OFF↑; 2 – ON↓ |
| *p-n-p* | 1 – ON↓; 2 – OFF↑ |

<a id="topic-39684"></a>

### Connecting load to the outputs

Outputs can be made in the form of electromagnetic relays (P), transistor (K) or triac (C) optocouplers. The outputs are used for direct load control (on/off) or for control by more powerful elements: contactors, solid state relays, thyristors or triacs. The outputs are galvanically isolated from the circuit of the device.

Scheme of connecting the load to the electromagnetic relay is shown in [Figure](#СхемаПодключенияНагрузкиКВУТипаР-29138F73).

<a id="СхемаПодключенияНагрузкиКВУТипаР-29138F73"></a>

![нагр к ВУ Р 0000001598](https://docs.owen.ru/book_img/813/100664.png)

*Scheme of connecting load to the output of type Р*

A transistor optocoupler is usually used to control a low-voltage relay (up to 50 V) – see [Figure](#СхемаПодключенияНагрузкиКВУТипаК-29139189).

> [!WARNING]
> **Caution.** The diode VD1 (KD103 or similar type) should be installed in parallel to the relay coil, in order to avoid failure of the transistor due to the large self-induction current.

<a id="СхемаПодключенияНагрузкиКВУТипаК-29139189"></a>

![нагр к ВУ К 0000001597](https://docs.owen.ru/book_img/813/100663.png)

*Scheme of connecting load to the output of type К*

The optosimistor is connected to the control circuit of the power triac through the limiting resistor R1 according to the scheme shown in [Figure](#СхемаПодключенияСиловогоСимистораКВ-29139F63).

> [!IMPORTANT]
> **Notice.** Nominal value of the resistor determines the current of the triac.

<a id="СхемаПодключенияСиловогоСимистораКВ-29139F63"></a>

![симистор ВУ С 0000001596](https://docs.owen.ru/book_img/813/100662.png)

*Scheme of connecting a power triac to the output of type C*

Optosimistor can also control a pair of anti-parallel connected thyristors (see [Figure](#СхемаПодключенияДвухВстречно-паралл-2913A09D)).

<a id="СхемаПодключенияДвухВстречно-паралл-2913A09D"></a>

![тиристоры ВУ С 0000001595](https://docs.owen.ru/book_img/813/100691.png)

*Scheme of connecting two anti-parallel connected thyristors to the output of type С*

> [!WARNING]
> **Caution.** It is recommended to connect a filtering circuit (RC) to the terminals of thyristors or triacs in order to prevent breakdown due to high-voltage power surges in the network.

<a id="topic-39685"></a>

## Operation of the device

<a id="topic-39686"></a>

### Principle of operation

Functional diagram of the device is shown in [Figure](#ФункциональнаяСхемаПрибора-3B3B026A).

<a id="ФункциональнаяСхемаПрибора-3B3B026A"></a>

![+Функциональная схема 0000001594](https://docs.owen.ru/book_img/813/100690.png)

*Functional diagram*

The device has four independent digital <b>*inputs*</b> for external control signals. To <b>*the inputs*</b> can be connected:

- switching devices (buttons, switches, reed switches, relays, etc.);
- sensors with output *n-p-n*-transistor with an open collector;
- sensors with output *p-n-p*-transistor.

The levels of the input signals are converted and processed in <b>*the matching unit*</b> and then sent to <b>*the digital signal processing unit*</b> that performs:

- reassignment of inputs in accordance with the selected counting mode (see [section](#topic-39691));
- filtering of input signals (see [section](#topic-39688));
- counting incoming pulses on the device inputs;
- convertion of the value from the counter into real physical value;
- comparing signal value to the setpoint before displaying;
- generation of signals for controlling the <b>*outputs*</b> according to a specified algorithm.

<b>*Control unit*</b> includes buttons for entering parameters of the device.

<b>*Display unit*</b> displays the measurement results or operating parameters on the indicators and shows the counter status using LEDs.

<b>*Secondary power supply*</b> converts the incoming voltage for all units of the device, depending on the version (with AC or DC power supply), and generates a signal indicating the loss of supply voltage.

The device can be connected with PC using <b>*RS-485*</b> and <b>*USB*</b> interfaces that allow to set and edit the device configuration, monitor its current status and indications.

<a id="topic-39687"></a>

### Control and indication

Elements of indication and control are located on the front panel of the device (see [Figures](#ЛицеваяПанельПрибораДляКорпусовНаст-41CC9A29) [and](#ЛицеваяПанельПрибораДляКорпусаЩитов-41CC9C6D)):

- two seven-segment six-digit digital indicators, red and green – see [Table](#НазначениеЦифровогоИндикатора-B953AB46);
- six/eight LEDs (depending on the construction type) – see [Table](#НазначениеСветодиодов-B5493DC2);
- four/five buttons (depending on the construction type) – see [Table](#НазначениеКнопок-B5493EDA).

All elements are placed on two (in housings Щ1 and Н) or on three printed circuit boards (in housing Щ2).

![Лицо Н и Щ1 0000001603](https://docs.owen.ru/book_img/813/100699.png)

![Лицо Щ2 0000001602](https://docs.owen.ru/book_img/813/100698.png)

<a id="ЛицеваяПанельПрибораДляКорпусовНаст-41CC9A29"></a>

*Front panel of the device in housings for wall-mounting H and panel-mounting Щ1*

<a id="ЛицеваяПанельПрибораДляКорпусаЩитов-41CC9C6D"></a>

*Front panel of the device in housing for panel-mounting Щ2*

**<a id="НазначениеЦифровогоИндикатора-B953AB46"></a>Assignment of digital indicators**

| Indicator | Operating mode of the device | Displayed information |
| --- | --- | --- |
| Upper indicator (red) | Operation | Current counter value |
| Upper indicator (red) | Setup | Name of the selected parameter |
| Lower indicator (green) | Operation | Setpoint value |
| Lower indicator (green) | Setup | Parameter value |

<a id="НазначениеСветодиодов-B5493DC2"></a>

**LEDs assignment**

| LED | Status | Description |
| --- | --- | --- |
| ![Светодиод замок 0000001621](https://docs.owen.ru/book_img/813/100697.png) | lights | Key lock is on |
| ![Светодиод Уст1 0000001620](https://docs.owen.ru/book_img/813/100696.png)<br>![Светодиод Уст2 0000001619](https://docs.owen.ru/book_img/813/100695.png) | lights | Number of setpoint (1 or 2) that is currently displayed on the lower indicator |
| ![Светодиод плюс-минус 0000001618](https://docs.owen.ru/book_img/813/100694.png) | lights | Direct counting |
| ![Светодиод плюс-минус 0000001618](https://docs.owen.ru/book_img/813/100694.png) | extinguished (off) | Reverse counting |
| ![Светодиод Выход 1 0000001617](https://docs.owen.ru/book_img/813/100693.png)<br>![Светодиод Выход2 0000001616](https://docs.owen.ru/book_img/813/100692.png) | lights | Сurrently enabled output |
| ![Светодиод сброс 0000001615](https://docs.owen.ru/book_img/813/100711.png)\* | lights | Input Reset is enabled |
| ![Светодиод блок 0000001614](https://docs.owen.ru/book_img/813/100710.png)\* | lights | Input Lock is enabled |

> [!IMPORTANT]
> **Notice.** \* LEDs ![Светодиод сброс 0000001615](https://docs.owen.ru/book_img/813/100711.png) and ![Светодиод блок 0000001614](https://docs.owen.ru/book_img/813/100710.png) are not available on the housing Щ2.

<a id="НазначениеКнопок-B5493EDA"></a>

**Buttons assignment**

| Button | Operating mode of the device | Functions |
| --- | --- | --- |
| ![Кнопка сброс 0000001613](https://docs.owen.ru/book_img/813/100709.png) | Operation | Resetting (similar to incoming "Reset" signal on the device input) |
| ![Кнопка сброс 0000001613](https://docs.owen.ru/book_img/813/100709.png) | Setup | Return previous (non-changed) value of the parameter during editing |
| ![Кнопка прог 0000001612](https://docs.owen.ru/book_img/813/100708.png) | Operation | Change the values of setpoints |
| ![Кнопка прог 0000001612](https://docs.owen.ru/book_img/813/100708.png) | Setup | • Enter and exit the settings group<br>• Enter the parameter editing mode and exit<br>• Save the new parameter value in non-volatile memory of the device |

Pressing at the same time buttons ![Кнопка сброс 0000001613](https://docs.owen.ru/book_img/813/100709.png) and ![Кнопка прог 0000001612](https://docs.owen.ru/book_img/813/100708.png) and holding them for 2 sec opens access to configuration setup (PC-interface parameters).

| Button | Operating mode of the device | Functions |
| --- | --- | --- |
| ![Кнопка лево 0000001631](https://docs.owen.ru/book_img/813/100707.png) | Operation | Select the digit to edit when changing the parameter value or entering the password (used with the buttons ![Кнопка вверх 0000001630](https://docs.owen.ru/book_img/813/100706.png) and ![Кнопка вниз 0000001629](https://docs.owen.ru/book_img/813/100705.png)) |
| ![Кнопка лево 0000001631](https://docs.owen.ru/book_img/813/100707.png) | Setup | Select the digit to edit when changing the parameter value or entering the password (used with the buttons ![Кнопка вверх 0000001630](https://docs.owen.ru/book_img/813/100706.png) and ![Кнопка вниз 0000001629](https://docs.owen.ru/book_img/813/100705.png)) |
| ![Кнопка вверх 0000001630](https://docs.owen.ru/book_img/813/100706.png)<br>![Кнопка вниз 0000001629](https://docs.owen.ru/book_img/813/100705.png)\* | Operation | Change the values of setpoints |
| ![Кнопка вверх 0000001630](https://docs.owen.ru/book_img/813/100706.png)<br>![Кнопка вниз 0000001629](https://docs.owen.ru/book_img/813/100705.png)\* | Setup | View parameter values and edit them,enter a password |

> [!IMPORTANT]
> **Notice.** \* The button ![Кнопка вниз 0000001629](https://docs.owen.ru/book_img/813/100705.png) is not available on the housing Щ2.

<a id="topic-39688"></a>

### Switch on and operation

During operation, the device counts the number of incoming pulses at its counting input, compares it with setpoint, converts this quantity into a physical value, and displays the value on the indicator. Device can operate in following modes of counting:

- count-up;
- count-down;
- command;
- individual;
- reversing;
- quadrature.

During operation the counter interprets different **types of signals**. On the device input first incoming pulse is considered as **Start** signal for counting. Counting stops when the **Stop** signal (next pulse) comes.

If there is an active "**Reset**" signal, the number of counted pulses is reset (counting continues from 0).

**Block** prevents the transmission of the counting pulses to the device input. While this signal is active, counting is blocked.

> [!WARNING]
> **Caution.** The setpoint is specified with the same accuracy as for counting physical values.. The multiplier can be set from 0.00001 to 99999. The conversion of counting results (result of multiplying) will be rounded up.

Read more about each of the counting modes, see [section](#topic-39691).

The counter also **filters** the input signals with two filters. The **first** one filters the signal on the counting input by pulse duration (from 1 to 50,000 Hz), the **second** filters signal on the control inputs of the device (from 1 to 999999 microseconds).

<a id="topic-39689"></a>

## Setup

<a id="topic-39690"></a>

### Sequence of setup

The **Setup** mode is intended for viewing and editing the device parameters. New parameters are saved to non-volatile memory of the device.

To enter (or exit) the **Setup** mode, press and hold button ![Кнопка прог 0000001612](https://docs.owen.ru/book_img/813/100708.png) for at least 2 seconds.For access to configuration setup (parameters of connection with PC) press at the same time buttons ![Кнопка сброс 0000001613](https://docs.owen.ru/book_img/813/100709.png) and ![Кнопка прог 0000001612](https://docs.owen.ru/book_img/813/100708.png) and hold them for 2 sec.

While editing, if no button is pressed within 2 min., device automatically restores previous value of the parameter and returns to parameter view mode. If within 3 minutes there are no actions in **Setup** menu, device automatically returns to **Operation**.

When device enters **Setup** for the first time, upper indicator shows `PASS`. Enter a new 4-digit password (default is 0000), save it and memorise. This password is further required for changing the device settings and for restoring factory settings (`dEFAUL`).

> [!IMPORTANT]
> **Notice.** If you forgot your password, **Setup** mode can be entered with password **1098**. When this value is entered, password is reset to 0000. Therefore, it is not recommended to set the new user password as 1098, because in this case, each time the password is entered, its value will be reset to default.

Structure of the **device settings** menu and sequence of pressing the buttons for setup is shown in [figure](#МенюНастроекПрибораначало-3B3BC9B7) and [figure](#МенюНастроекПрибораокончание-3B3BCB0A).

<a id="МенюНастроекПрибораначало-3B3BC9B7"></a>

![параметры настройки 1 0000001628](https://docs.owen.ru/book_img/813/100704.png)

*Device settings menu (beginning)*

<a id="МенюНастроекПрибораокончание-3B3BCB0A"></a>

![параметры настройки 2 0000001627](https://docs.owen.ru/book_img/813/100703.png)

*Device settings menu (ending)*

Since the `FDP` and `DP` parameters set restrictions on each other (the number of displayed digits after the decimal point in the counting results can not be larger than the number of digits after the decimal point of the entered multiplier), editing of parameters `FDP`, `DP`, `F` should be performed in the following sequence:

- to increase the number of displayed digits after the decimal point (decimal point offset to the left):

  - set parameter `FDP`;
  - set parameter `F`;
  - set parameter `DP`;

- to decrease the number of displayed digits after the decimal point (decimal point offset to the right):

  - set parameter `DP`;
  - set parameter `FDP`;
  - set parameter `F`.

Structure of the **RS-485 configuration settings** menu and sequence of pressing the buttons for setup is shown in [Figure](#МенюНастроекRS-485-3B3BCD1C).

> [!IMPORTANT]
> **Notice.** The list of configurable parameters of the device and their possible values is shown in [Appendix](#topic-39699).

<a id="МенюНастроекRS-485-3B3BCD1C"></a>

![параметры настройки RS-485 0000001626](https://docs.owen.ru/book_img/813/100702.png)

*RS-485 settings menu RS-485*

<a id="topic-39691"></a>

### Operating modes

Availiable types of counting (depending on the values of parameter `inP`) are presented in [Table](#TypesOfCounting-A38E986C).

<a id="TypesOfCounting-A38E986C"></a>

**Types of counting**

| Mode | Description |
| --- | --- |
| Count-up<br>(`inP = 1`) | Input functions: Input 1 – count, Input 2 – start/stop, Input 3 – reset, Input 4 – block<br>Operating principle: Pulse count from zero upwards. When the setpoint is reached, the corresponding output is switched and the counter is reset<br>![Диаграмма прямой 0000001593](https://docs.owen.ru/book_img/813/100689.png)<br>{t<sub>1</sub>–t<sub>2</sub>} – blocking signal the counting inputs;<br>t<sub>3</sub> – switching of output 2 in case of coincidence of values of the counting register and setpoint 2;<br>{t<sub>4</sub>–t<sub>5</sub>} – stop-start signal;<br>t<sub>6</sub> – switching of output 1 in case of coincidence of values of the counting register and setpoint 1 |
| Count-down<br>(`inP = 2`) | Input functions: Input 1 – count, Input 2 – start/stop, Input 3 – reset, Input 4 – block<br>Operating principle: Counting pulseopw6z7ds from the highest by the module setpoint to zero (decreasing). When the zero is reached, corresponding output is switched and the setpoint register is written to the count register<br>![Диаграмма обратн 0000001592](https://docs.owen.ru/book_img/813/100688.png)<br>{t<sub>1</sub>–t<sub>2</sub>} – blocking signal on the counting inputs;<br>t<sub>3</sub> – moment of switching of output 2 in case of coincidence of values of the counting register and setpoint 2;<br>{t<sub>4</sub>–t<sub>5</sub>} – stop-start signal;<br>t<sub>6</sub> – moment of switching of output 1 in case of coincidence of values of the counting register and setpoint 1 |
| Command count<br>(`inP = 3`) | Input functions: Input 1 – count, Input 2 - direction of count, Input 3 – reset, Input 4 – block<br>Operating principle:<br>Two inputs are used: counting pulses are applied to the first, the status of the second determines the direction of the count. If there is a "logical 0" at the second output, the counter increases its value, if there is a "logical 1" it decreases. In this type two setpoints can be set, meanwhile:<br>• if the setpoints have the same sign, counter resets after reaching the setpoint, that is larger by module.<br>![Диаграмма команд одинак 0000001611](https://docs.owen.ru/book_img/813/100687.png)<br>{t<sub>1</sub>–t<sub>2</sub>} – the decrease in the value of the counting register (impulse appears at the counting input 2);<br>t<sub>3</sub> – moment of switching of output 2 in case of coincidence of values of the counting register and setpoint 2;<br>t<sub>4</sub> – moment of switching of output 1 in case of coincidence of values of the counting register and setpoint 1<br>• if the setpoints have different signs, the counter is reset after reaching each value<br>![Диаграмма команд разн 0000001610](https://docs.owen.ru/book_img/813/100686.png)<br>{t<sub>1</sub>–t<sub>3</sub>} – the decrease in the value of the counting register (impulse appears at the counting input 2);<br>t<sub>2</sub> – moment of switching of output 2 in case of coincidence of values of the counting register and setpoint 2;<br>t<sub>4</sub> – moment of switching of output 1 in case of coincidence of values of the counting register and setpoint 1<br>**Notice.** If the setpoint is set as zero, it is considered to be disabled, and the counter does not use it. |
| Individual count<br>(`inP = 4`) | Input functions: Input 1 – count 1, Input 2 – count 2, Input 3 – reset, Input 4 – block<br>Two counting inputs are used: pulses on Input 1 increase the value of the counting register, and the pulses on Input 2 decrease it. In this case, two setpoints are used (after reaching each of them, the corresponding output switches):<br>Operating principle:<br>• if both setpoints have the same sign, counter does not reset after reaching lesser (by module) value. Otherwise, corresponding output is switched each time counter reaches this setpoint, regardless of the direction of the count<br>![Диаграмма индив одинак 0000001609](https://docs.owen.ru/book_img/813/100685.png)<br>t<sub>1</sub>, t<sub>3</sub>, t<sub>5</sub> – moments of the decrease in the value of the counting register (impulse appears at the counting input 2);<br>t.<sub>2</sub> – moment of switching of output 2 in case of coincidence of values of the counting register and setpoint 2;<br>t<sub>4</sub> – moment of switching of output 1 in case of coincidence of values of the counting register and setpoint 1<br>• if the setpoints have different signs (the first is greater than zero, and the second is smaller), then counter resets after reaching each setpoints<br>![Диаграмма индив разн 0000001608](https://docs.owen.ru/book_img/813/100684.png)<br>t<sub>1</sub>, t<sub>3</sub> – moments of the decrease in the value of the counting register (the appearance of the pulse at the counting input 2);<br>t<sub>2</sub> – moment of switching of output 2 in case of coincidence of values of the counting register and setpoint 2;<br>t<sub>4</sub> – moment of switching of output 1 in case of coincidence of values of the counting register and setpoint 1 |
| Reversing count<br>(`inP = 5`) | Input functions: Input 1 – count 1, Input 2 – change counting direction (reverse), Input 3 – reset, Input 4 – block<br>Operating principle:<br>After the power is on, the device is in the "count-up" mode by default. For reversing count it is necessary to apply signal to input 2.<br>Thus there are two counting inputs: pulses on Input 1, lead to an increase in the value of the counter, the counting direction is changed cyclically with each incoming pulse on Input 2. In this case, two setpoints are used (after reaching each of them, the corresponding output switches):<br>• if both the setpoints have the same sign<br>![Диаграмма реверс одинак 0000001607](https://docs.owen.ru/book_img/813/100683.png)<br>t<sub>1</sub>, t<sub>2</sub> – moments of change of the counting direction (the appearance of the pulse at the counting input 2);<br>t<sub>3</sub> – moment of switching of output 2 in case of coincidence of values of the counting register and setpoint 2;<br>t<sub>4</sub> – moment of switching of output 1 in case of coincidence of values of the counting register and setpoint 1<br>• if the setpoints have different signs<br>![Диаграмма реверс разн 0000001606](https://docs.owen.ru/book_img/813/100682.png)<br>t<sub>1</sub>, t<sub>3</sub> – moments of change of the counting direction (the appearance of the pulse at the counting input 2);<br>t<sub>2</sub> – moment of switching of output 2 in case of coincidence of values of the counting register and setpoint 2;<br>t<sub>4</sub> – moment of switching of output 1 in case of coincidence of values of the counting register and setpoint 1 |
| Quadrature / operation with encoders<br>(`inP = 6`) | Input functions: Input 1 – count 1, Input 2 – count 2, Input 3 – reset, Input 4 – block<br>Operating principle:<br>The counting direction is determined by the meanders that come on two inputs. If the first meander is ahead of the second one, the counter counts the pulses at the first input in the increase mode, and if it lags – in the decrease mode. In this case, two setpoints are used (after reaching each of them, the corresponding output switches):<br>• if both the setpoints have the same sign<br>![Диаграмма квадрат одинак 0000001605](https://docs.owen.ru/book_img/813/100701.png)<br>t<sub>1</sub>, t<sub>2</sub>, t<sub>5</sub>, t<sub>6</sub> – meander at input 1 is ahead of the meander at the input 2,<br>the counter counts in the mode of increasing the value of the count register;<br>t<sub>3</sub>, t<sub>4</sub> – the meander at input 1 lags behind the meander at input 2,<br>the counter counts in the mode of decreasing the value of the counting register;<br>t<sub>7</sub> – moment of switching of output 2 for the time of exceeding the value of setpoint 2 by the counting register;<br>t<sub>8</sub> – moment of switching of output 1 for the time of exceeding the value of setpoint 1 by the counting register<br>• if setpoints have different signs<br>![Диаграмма квадрат разн 0000001604](https://docs.owen.ru/book_img/813/100700.png)<br>t<sub>1</sub>, t<sub>2</sub> – the meander at input 1 lags behind the meander at input 2,<br>the counter counts in the mode of increasing the value of the count register;<br>t<sub>3</sub> – moment of switching of output 2 in case of coincidence of values of the counting register and the setpoint 2;<br>t<sub>4</sub>, t<sub>5</sub> – the meander at input 1 is ahead of the meander at input 2,<br>the counter counts in the mode of increasing the value of the count register;<br>t<sub>6</sub> – moment of switching of output 1 in case of coincidence of values of the counting register and the setpoint 1<br>**Note.** After reaching the physical limit of the count (if the counter does not reset after reaching the setpoint), the device transfers the overflow result and continues the count. |

<a id="topic-39692"></a>

### Configuring the device from PC

Device can be configured from PC by using RS-485 and USB communication interfaces. It supports three communication protocols: OWEN, MODBUS RTU и MODBUS ASCII. Addresses, names, dimensionalities, hash-codes and other configuration parameters are given in [Appendix](#topic-39699).

Functions of the software "Configurator СИ30" (file <b>*cfgSI30.exe*</b>), which is designed for configuring the device with PC, are described in the user manual "Pulse counter, model СИ30. Configuration" on the CD supplied. The configurator can be downloaded free from the website: www.owen.ru.

Parameters for reading indications of the counter from PC are described in [Table](#СчитываемыеПараметры-3B3C73BF).

<a id="topic-39693"></a>

## Maintenance

Safety measures (see [section](#topic-39674)) should be observed during the maintenance.

Maintenance of the device has to be carried out at least once in 6 months and includes the following procedures:

- checking the mounting of the device;
- checking the screw connections;
- removing dust and dirt from the terminal block of the device.

<a id="topic-39694"></a>

## Marking

The housing of the device is marked with:

- name of the device;
- protection class of the housing according to GOST 14254;
- voltage and frequency of supply;
- power consumption;
- class of protection against electric shock according to GOST 12.2.007.0;
- sign of type approval for measuring devices;
- EAC sign;
- country of origin;
- serial number of the device and the year of manufacture.

Consumer packaging is marked with:

- name of the device;
- EAC sign;
- country of origin;
- serial number of the device and the year of manufacture.

<a id="topic-39695"></a>

## Packaging

Device should be packed according to GOST 23088-80 into consumer packaging, made of paperboard (according to GOST 7933-89).

Packaging of the device for mail delivery is performed according to GOST 9181-74.

<a id="topic-39696"></a>

## Transportation and storage

The device should be transported in closed vehicles of any kind. Packages should be fixed for transportation according to rules for corresponding type of vehicle.

Transport conditions must comply with conditions 5 in GOST 15150-69 (ambient temperature from minus 25 to +55 °C with observance of protection measures against impacts and vibrations).

Transportation should be carried out in individual packaging or in containers.

Storage conditions in containers on the warehouse of the manufacturer and consumer must correspond to conditions 1 in GOST 15150-69. The air must not contain aggressive admixtures.

The device should be stored on racks.

<a id="topic-39697"></a>

## Scope of delivery

| Item | Quantity |
| --- | --- |
| The device | 1 piece |
| Passport and warranty card | 1 piece |
| User manual | 1 piece |
| The verification procedure (at the request of the customer) | 1 piece |
| Fasteners | 1 set |
| CD with the software | 1 piece |

> [!IMPORTANT]
> **Notice.** The manufacturer reserves the right to make additions to the contents of the device.

<a id="topic-39698"></a>

## Warranty

The manufacturer guarantees conformity of the device to requirements of technical conditions (ТУ) under the conditions of operation, transportation, storage and installation.

Warranty period of operation – **24 months** from the date of sale.

In case of failure of the device during the warranty period at observance of conditions of operation, transportation, storage and installation the manufacturer undertakes to provide free repair or replacement.

Sequence of transmitting the device to service center is written in the passport and in the warranty card.

<a id="topic-39699"></a>

## Device parameters

**Configurable parameters**

| **Parameter name and designation** | **Modbus address** | **Modbus function**<br>**Write / Read** | **Hash-code** | **Format, data size** | **Range of values and indication** | **Factory settings** |
| --- | --- | --- | --- | --- | --- | --- |
| Setpoint 1<br>`U1` | 0×000C<br>0×000D | 0×06, 0×10 / 0×03 | 0×FA1E | Long<br>(4 bytes) | from minus 99999 to 999999 | 999999 |
| Setpoint 2<br>`U2` | 0×000E<br>0×000F | 0×06, 0×10 / 0×03 | 0×9707 | Long<br>(4 bytes) | from minus 99999 to 999999 | 0 |
| Counting mode<br>`inP` | 0×0008 | 0×06, 0×10 / 0×03 | 0×38D9 | Word<br>(2 bytes) | 0 – Count-up (`1`) | Count-up |
| Counting mode<br>`inP` | 0×0008 | 0×06, 0×10 / 0×03 | 0×38D9 | Word<br>(2 bytes) | 1 – Count-down (`2`) | Count-up |
| Counting mode<br>`inP` | 0×0008 | 0×06, 0×10 / 0×03 | 0×38D9 | Word<br>(2 bytes) | 2 – Command (`3`) | Count-up |
| Counting mode<br>`inP` | 0×0008 | 0×06, 0×10 / 0×03 | 0×38D9 | Word<br>(2 bytes) | 3 – Individual (`4`) | Count-up |
| Counting mode<br>`inP` | 0×0008 | 0×06, 0×10 / 0×03 | 0×38D9 | Word<br>(2 bytes) | 4 – Reversing (`5`) | Count-up |
| Counting mode<br>`inP` | 0×0008 | 0×06, 0×10 / 0×03 | 0×38D9 | Word<br>(2 bytes) | 5 – Quadrature (`6`) | Count-up |
| Output mode<br>`oUt` | 0×0009 | 0×06, 0×10 / 0×03 | 0×D11F | Word<br>(2 bytes) | 0 – Switched after setpoint (`1`) | Switched after setpoint |
| Output mode<br>`oUt` | 0×0009 | 0×06, 0×10 / 0×03 | 0×D11F | Word<br>(2 bytes) | 1 – Switched before setpoint`(2`) | Switched after setpoint |
| Output mode<br>`oUt` | 0×0009 | 0×06, 0×10 / 0×03 | 0×D11F | Word<br>(2 bytes) | 2 – Switched for a time after the setpoint (`3`)\* | Switched after setpoint |
| Output mode<br>`oUt` | 0×0009 | 0×06, 0×10 / 0×03 | 0×D11F | Word<br>(2 bytes) | 3 – Switched when multiple setpoint values (`4`) | Switched after setpoint |

> [!IMPORTANT]
> **Notice.** \* After reaching the setpoint the output is switched for a time period, that is specified in parameteres `t1`  and `t2`, the count value is reset and the counting continues from zero (parameter `SPM = RESET`).

| **Parameter name and designation** | **Modbus address** | **Modbus function**<br>**Write / Read** | **Hash-code** | **Format, data size** | **Range of values and indication** | **Factory settings** |
| --- | --- | --- | --- | --- | --- | --- |
| Time period for output 1<br>`t1` | 0×0010<br>0×0011 | 0×06, 0×10 / 0×03 | 0×2E75 | Unsigned long<br>(4 bytes) | from 0 to 999990 ms | 1000 ms |
| Time period for output 2<br>`t2` | 0×0012<br>0×0013 | 0×06, 0×10 / 0×03 | 0×436C | Unsigned long<br>(4 bytes) | from 0 to 999990 ms | 1000 ms |
| Decimal point position multiplier<br>`FDP` | 0×0014 | 0×06, 0×10 / 0×03 | 0×6ABF | Word<br>(2 bytes) | 0 (`------`) | 0 |
| Decimal point position multiplier<br>`FDP` | 0×0014 | 0×06, 0×10 / 0×03 | 0×6ABF | Word<br>(2 bytes) | 1 (`-----.-`) | 0 |
| Decimal point position multiplier<br>`FDP` | 0×0014 | 0×06, 0×10 / 0×03 | 0×6ABF | Word<br>(2 bytes) | 2 (`----.--`) | 0 |
| Decimal point position multiplier<br>`FDP` | 0×0014 | 0×06, 0×10 / 0×03 | 0×6ABF | Word<br>(2 bytes) | 3 (`---.---`) | 0 |
| Decimal point position multiplier<br>`FDP` | 0×0014 | 0×06, 0×10 / 0×03 | 0×6ABF | Word<br>(2 bytes) | 4 (`--.----`) | 0 |
| Decimal point position multiplier<br>`FDP` | 0×0014 | 0×06, 0×10 / 0×03 | 0×6ABF | Word<br>(2 bytes) | 5 (`-.-----`) | 0 |
| Multiplier<br>`F` | 0×0015<br>0×0016 | 0×06, 0×10 / 0×03 | 0×3085 | Unsigned long<br>(4 bytes) | from 0.00001 to 99999 | 1 |
| Position of the decimal point<br>`DP` | 0×0007 | 0×06, 0×10 / 0×03 | 0×B3EB | Word<br>(2 bytes) | 0 (`------`) | 0 |
| Position of the decimal point<br>`DP` | 0×0007 | 0×06, 0×10 / 0×03 | 0×B3EB | Word<br>(2 bytes) | 1 (`-----.-`) | 0 |
| Position of the decimal point<br>`DP` | 0×0007 | 0×06, 0×10 / 0×03 | 0×B3EB | Word<br>(2 bytes) | 2 (`----.--`) | 0 |
| Position of the decimal point<br>`DP` | 0×0007 | 0×06, 0×10 / 0×03 | 0×B3EB | Word<br>(2 bytes) | 3 (`---.---`) | 0 |
| Position of the decimal point<br>`DP` | 0×0007 | 0×06, 0×10 / 0×03 | 0×B3EB | Word<br>(2 bytes) | 4 (`--.----`) | 0 |
| Type of work after reaching setpoint<br>`SPM` | 0×000A | 0×06, 0×10 / 0×03 | 0×69B2 | Word<br>(2 bytes) | 0 – Continue counting without resetting(`CONT`) | Continue counting without resetting |
| Type of work after reaching setpoint<br>`SPM` | 0×000A | 0×06, 0×10 / 0×03 | 0×69B2 | Word<br>(2 bytes) | 1 – Stop the counting until a "RESET" signal<br>(`STOP`) | Continue counting without resetting |
| Type of work after reaching setpoint<br>`SPM` | 0×000A | 0×06, 0×10 / 0×03 | 0×69B2 | Word<br>(2 bytes) | 2 – Reset the counter and continue counting<br>(`RESET`) | Continue counting without resetting |
| Type of work to "Reset" signal<br>`rSt` | 0×000B | 0×06, 0×10 / 0×03 | 0×4C9A | Word<br>(2 bytes) | 0 – Reset the counter(`1`) | Reset the counter |
| Type of work to "Reset" signal<br>`rSt` | 0×000B | 0×06, 0×10 / 0×03 | 0×4C9A | Word<br>(2 bytes) | 1 – Reset the counter and disable output signals (`2`) | Reset the counter |
| Type of work to "Reset" signal<br>`rSt` | 0×000B | 0×06, 0×10 / 0×03 | 0×4C9A | Word<br>(2 bytes) | 2 – Reset the counter and wait for signal "Start" (`3`) | Reset the counter |
| Type of work to "Reset" signal<br>`rSt` | 0×000B | 0×06, 0×10 / 0×03 | 0×4C9A | Word<br>(2 bytes) | 3 – Reset the counter and wait for signal "Stop" (`4`) | Reset the counter |
| Frequency of the input filter<br>`FREQ` | 0×0017 | 0×06, 0×10 / 0×03 | 0×9FE6 | Word<br>(2 bytes) | from 1 to 50000 Hz | 50000 Hz |
| Minimum duration of the signal on the control inputs<br>`Cnt.t` | 0×0018<br>0×0019 | 0×06, 0×10 / 0×03 | 0×5C98 | Unsigned long<br>(4 bytes) | from 10 to 9999990 microseconds | 10 microseconds |
| Input logic<sup>1)</sup><br>(type of input signal)<br>`SiG` | 0×001D | 0×06, 0×10 / 0×03 | 0×601C | Word<br>(2 bytes) | 0 – `nPn` | nPn |
| Input logic<sup>1)</sup><br>(type of input signal)<br>`SiG` | 0×001D | 0×06, 0×10 / 0×03 | 0×601C | Word<br>(2 bytes) | 1 – `PnP` | nPn |
| Brightness of the indicator<br>`brHt` | 0×001C | 0×06, 0×10 / 0×03 | 0×0AE6 | Word<br>(2 bytes) | from 0 to 3 (`1` – `4`) | 3 |
| Lock buttons<br>`LoCK` | 0×001A | 0×06, 0×10 / 0×03 | 0×E954 | Word<br>(2 bytes) | 0 – Buttons unlocked<br>(`oFF`) | Buttons unlocked |
| Lock buttons<br>`LoCK` | 0×001A | 0×06, 0×10 / 0×03 | 0×E954 | Word<br>(2 bytes) | 1 – Blocked counter reset (`1`) | Buttons unlocked |
| Lock buttons<br>`LoCK` | 0×001A | 0×06, 0×10 / 0×03 | 0×E954 | Word<br>(2 bytes) | 2 – Change of setpoints is blocked<br>(`2`) | Buttons unlocked |
| Lock buttons<br>`LoCK` | 0×001A | 0×06, 0×10 / 0×03 | 0×E954 | Word<br>(2 bytes) | 3 – Reset and change of setpoints are blocked (`3`) | Buttons unlocked |
| Restore factory settings<br>`dEFAUL` | – | – | – | – | `YES` / `no` | – |
| Password<br>`PASS` | 0×001E | 0×06, 0×10 / 0×03 | 0×2728 | Word<br>(2 bytes) | from 0000 to 9999 | 0000 |
| Displayed setpoint<sup>2)</sup><br>`ind2` | 0×001B | 0×06, 0×10 / 0×03 | 0×CAA0 | Word<br>(2 bytes) | 0 – Setpoint 1 | 0 |
| Displayed setpoint<sup>2)</sup><br>`ind2` | 0×001B | 0×06, 0×10 / 0×03 | 0×CAA0 | Word<br>(2 bytes) | 1 – Setpoint 2 | 0 |
| Command for applying settings<sup>2)</sup><br>`APPL` | – | – | – | – | 1 – Exit with saving | – |
| Command for applying settings<sup>2)</sup><br>`APPL` | – | – | – | – | 2 – Exit without saving | – |
| Command for applying settings<sup>2)</sup><br>`APPL` | – | – | – | – | 3 – Return to factory settings | – |

**RS-485 settings**

| **Parameter name and designation** | **Modbus address** | **Modbus function**<br>**Write / Read** | **Hash-code** | **Format, data size** | **Range of values and indication** | **Factory settings** |
| --- | --- | --- | --- | --- | --- | --- |
| RS-485 data transfer rate<br>`bPS` | 0×0000 | 0×06, 0×10 / 0×03 | 0×B760 | Word<br>(2 bytes) | 0 – 2400 | 9600 |
| RS-485 data transfer rate<br>`bPS` | 0×0000 | 0×06, 0×10 / 0×03 | 0×B760 | Word<br>(2 bytes) | 1 – 4800 | 9600 |
| RS-485 data transfer rate<br>`bPS` | 0×0000 | 0×06, 0×10 / 0×03 | 0×B760 | Word<br>(2 bytes) | 2 – 9600 | 9600 |
| RS-485 data transfer rate<br>`bPS` | 0×0000 | 0×06, 0×10 / 0×03 | 0×B760 | Word<br>(2 bytes) | 3 – 14400; 4 – 19200 | 9600 |
| RS-485 data transfer rate<br>`bPS` | 0×0000 | 0×06, 0×10 / 0×03 | 0×B760 | Word<br>(2 bytes) | 5 – 28800; 6 – 38400 | 9600 |
| RS-485 data transfer rate<br>`bPS` | 0×0000 | 0×06, 0×10 / 0×03 | 0×B760 | Word<br>(2 bytes) | 7 – 57600; 8 – 115200 | 9600 |
| Data word length<br>`LEn` | 0×0001 | 0×06, 0×10 / 0×03 | 0×523F | Word<br>(2 bytes) | 0 – 7 bit (`7 bit`) | 8 bit |
| Data word length<br>`LEn` | 0×0001 | 0×06, 0×10 / 0×03 | 0×523F | Word<br>(2 bytes) | 1 – 8 bit (`8 bit`) | 8 bit |
| Parity<br>`PrtY` | 0×0002 | 0×06, 0×10 / 0×03 | 0×E8C4 | Word<br>(2 bytes) | 0 – Without parity (`NO`) | Without parity |
| Parity<br>`PrtY` | 0×0002 | 0×06, 0×10 / 0×03 | 0×E8C4 | Word<br>(2 bytes) | 1 – Even parity<br>(`EVEN`) | Without parity |
| Parity<br>`PrtY` | 0×0002 | 0×06, 0×10 / 0×03 | 0×E8C4 | Word<br>(2 bytes) | 2 – Odd parity (`Odd`) | Without parity |
| Number of stop bits<br>`Sbit` | 0×0003 | 0×06, 0×10 / 0×03 | 0×B72E | Word<br>(2 bytes) | 0 – 1 stop bit | 1 stop bit |
| Number of stop bits<br>`Sbit` | 0×0003 | 0×06, 0×10 / 0×03 | 0×B72E | Word<br>(2 bytes) | 1 – 2 stop bits | 1 stop bit |
| Base address of the device<sup>3)</sup><br>`Addr` | 0×0005 | 0×06, 0×10 / 0×03 | 0×9F62 | Word<br>(2 bytes) | from 0 to 255 when `A.Len` = 8 | 16 |
| Base address of the device<sup>3)</sup><br>`Addr` | 0×0005 | 0×06, 0×10 / 0×03 | 0×9F62 | Word<br>(2 bytes) | from 0 до 2047 when `A.Len` =  11 | 16 |
| Length of network address<sup>2)</sup><br>`A.LEN` | 0×0004 | 0×06, 0×10 / 0×03 | 0×1ED2 | Word<br>(2 bytes) | 8 bit | 8 bit |
| Length of network address<sup>2)</sup><br>`A.LEN` | 0×0004 | 0×06, 0×10 / 0×03 | 0×1ED2 | Word<br>(2 bytes) | 11 bit | 8 bit |
| Response delay<br>RS-485<br>`rS.dL` | 0×0006 | 0×06, 0×10 / 0×03 | 0×CBF5 | Word<br>(2 bytes) | from 0 to 45 | 0 |

**Notes**

<sup>1)</sup> Setting of parameter `SiG` works only together with DIP switch (see [section](#topic-39683)).

<sup>2)</sup> Parameters that are not displayed in the **Setup** mode of the device.

<sup>3)</sup> In Modbus protocol address 0 is reserved for broadcast packages. In OWEN protocol address 255 is reserved for broadcast packages.

<a id="СчитываемыеПараметры-3B3C73BF"></a>

**Readable parameters**

| Designation and parameter name | Modbus address | Modbus function<br>Read-only | Hash-code | Format and size of data | Note |
| --- | --- | --- | --- | --- | --- |
| Current value of the pulse counter `Ctr` | 0×0000<br>0×0001 | 0×04 | 0×A158 | Long (4 bytes) | – |
| Current counter value in physical units `CEU` | 0×0002<br>0×0003 | 0×04 | 0×B8BC | Long (4 bytes) | – |
| Current status of the "Start/stop"<br>`StSt` | 0×0004 | 0×04 | 0×6577 | – | 0 – start;<br>1 – stop |
| Current mode (count, setup)<br>`CUR` | 0×0005 | 0×04 | 0×CC41 | Word (2 bytes) | 0 – count (password not required);<br>1 – setup from the device's buttons;<br>2 – setup from the PC;<br>3 – count (requires password) |
| Network error code on last access<br>to the device<br>`n.Err` | 0×0006 | 0×04 | 0×0233 | Word (2 bytes) | From 0 to 255.<br>After turning on the device – 0 |
| Name of the device<br>`DEV` | 0×0007<br>0×0008 | 0×04 | 0×D681 | ASCII string<br>(4 bytes) | – |
| Software version<br>`VER` | 0×0009<br>0×000А | 0×04 | 0×2D5B | ASCII string<br>(4 bytes) | X.YY,<br>where Х – number of version, YY – number of subversion |

**Bit parameters**

**Digital inputs**

| Designation and name of parameter | Modbus address | Modbus function<br>write / read | Hash-code | Format and size of data | Note |
| --- | --- | --- | --- | --- | --- |
| Current status of the "Reset" input<br>`rSti` | 0×0000 | – / 0×02 | 0×C010 | Byte (1 byte)<br>0 / 1 | – |
| Current status of the "Block" input<br>`Loci` | 0×0001 | – / 0×02 | 0×93EC | Byte (1 byte)<br>0 / 1 | – |

**Digital outputs**

| Designation and name of parameter | Modbus address | Modbus function<br>write / read | Hash-code | Format and size of data | Note |
| --- | --- | --- | --- | --- | --- |
| Status of output 1<br>`OSt1` | 0×0000 | – / 0×01 | 0×6FFD | Byte (1 byte)<br>0 / 1 | – |
| Status of output 2<br>`OSt2` | 0×0001 | – / 0×01 | 0×52A1 | Byte (1 byte)<br>0 / 1 | – |
| Reset of counter<br>`rStC` | 0×0002 | 0×05, 0×0F / 0×01 | 0×DF1F | Byte (1 byte)<br>0 / 1 | 0 – no action;<br>1 – reset |
| Enable/disable the program control mode counter START/STOP<br>`OnOff` | 0×0003 | 0×05 / – | – | – | 0 – OFF (0x0000);<br>1 – ON (0xFF00) |
| Command to set the program control mode counter START/STOP<br>`PStSt` | 0×0004 | 0×05 / – | – | – | 0 – STOP (0x0000);<br>1 – START (0xFF00) |